Our team through qualified training. Skilled professional knowledge, powerful sense of support, to satisfy the support desires of consumers for Recovery From Ventilator, Exhaust Ventilation Fan, Variable Speed Air Handler, "Passion, Honesty, Sound service, Keen cooperation and Development" are our goals. We are here expecting friends all over the world!
OEM/ODM Supplier Return Air Grille - Liquid Circulation Heat Exchangers – Holtop Detail:

Liquid Circulation Heat Exchanger 

Working Principle

Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers installed in both fresh air side and exhaust air side, the pump between the 2 heat

exchangers make the liquid circulate then the heat in the liquid preheat or precool the fresh air. Normally the liquid is water but in order to decrease the freezing point,

moderate ethylene glycol will be added into the water according to reasonable percentage.

Features

(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination.Suitable for hospital, germfree lab and industries which discharge

poisonous and harmful gas.

(2) Stable and reliable operation, long service life

(3) Flexible connection between fresh air and exhaust air exchangers, easy installation which is convenient for old AHU improvement.

(4) Accessories like water pump, heat exchangers are conventional, easy and low maintanence costs.

(5) Wide range of application, various connection ways like one to one, one to many or many to many.

Specifications

(1) Liquid circulation heat exchanger is sensible heat exchanger, efficiency is between 55% to 60%.

(2) Suggested rows are 6 or 8, face velocity not over 2.8m/s

(3) The choice of circulating pump can refer to the fresh air and exhuast air pressure drop and the waterflow pressure drop.

(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.

(5) Freezing point of the hybrid ethylene glycol and water should be 4 to 6 celsius lower than the local minimum winter outdoor temperature, percentage of hybridcan

be refered to the following table.

Freezing point -1.4 - 1.3 -5.4 -7.8 -10.7 -14.1 -17.9 -22.3
Weight percentage (%) 5 10 15 20 25 30 35 40
Volume percentage (% ) 4.4 8.9 13.6 18.1 22.9 27.7 32.6 37.5
5 6

Product detail pictures:

OEM/ODM Supplier Return Air Grille - Liquid Circulation Heat Exchangers – Holtop detail pictures

OEM/ODM Supplier Return Air Grille - Liquid Circulation Heat Exchangers – Holtop detail pictures


Related Product Guide:
LHT develops automated steam cleaner for engine heat exchangers | Silent Ventilation Fan
A systems approach to hygiene in food processing environments | Air Heat Exchangers

As for aggressive costs, we believe that you will be searching far and wide for anything that can beat us. We can state with absolute certainty that for such high-quality at such rates we have been the lowest around for OEM/ODM Supplier Return Air Grille - Liquid Circulation Heat Exchangers – Holtop, The product will supply to all over the world, such as: French, Ethiopia, Qatar, We sincerely hope to cooperate with customers all over the world, if you would like to have more information, please kindly contact us, we are looking forward to building up a great business relationship with you.
commercial heat recovery ventilator
Ductless Heat Recovery Ventilator
Heat Recovery Ventilators
Heat Recovery Ventilator
Hrv Heat Recovery Ventilator
Single Room Heat Recovery Ventilator

The company has rich resources, advanced machinery, experienced workers and excellent services, hope you keep improving and perfecting your products and service, wish you better!
5 Stars By Althea from Detroit - 2015.07.26 16:51
It is not easy to find such a professional and responsible provider in today's time. Hope that we can maintain long-term cooperation.
5 Stars By Abigail from Auckland - 2015.11.11 19:52

Related Products